6.1 Braking Modules
Booksize power units
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
407
Note
Applying a high signal to terminal X21.1 inhibits the Braking Module. On a falling edge,
pending error signals are acknowledged.
The pre-warning for I*t monitoring is output as a high level on reaching 80% of the maximum
braking resistor ON time.
Only braking resistors approved by Siemens for this component are identified automatically.
6.1.3.5 Meaning of the LEDs on the Braking Module
Table 6-3 Braking Module Booksize – description of the LEDs
LED Color Status Description, cause Remedy
- off Electronics power supply is missing or outside permissible
tolerance range.
Component deactivated via terminal.
Green Continuous Component is ready to operate.
READY
Red Continuous Overtemperature
Overcurrent switch-off
I
2
t monitoring activated.
Ground fault/short-circuit.
Note:
In the event of an overtemperature, the error cannot be
acknowledged until a cooling time has elapsed.
Diagnose fault (via
output terminals) and
acknowledge it (via
input terminal)
- off Electronics power supply is missing or outside permissible
tolerance range.
Component not active.
DC LINK
Green Flashing Component active (DC link discharge via braking resistor in
progress).