Booksize DC Link Components
6.4 Voltage Clamping Module
Booksize power units
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
431
9ROWDJH&ODPSLQJ0RGXOH
;
'&3
'&1
'&3
'&1
0
0
Figure 6-15 Circuit diagram: Voltage Clamping Module
6.4.3.2 X1 functional ground
X1 functional ground
To ensure that the Voltage Clamping Module functions properly, a functional ground must be
connected to X1. Please note:
The cables must be routed via the shortest possible path
Cross-section: 4 mm² to 16 mm²
When a line filter is used, the functional ground should be located on the metallic
installation panel in the immediate vicinity of the line filter.
In systems without a line filter, it should be connected on the PE busbar.