Service and Support Booksize
10.4 Spare parts
Booksize power units
554 Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
0RWRU
FRQQHFWLRQ
/ / / 3(
9$&
8
9
:
0RWRUPRGXOH
'&3
'&1
3(
)XVHGVZLWFK
/LJKWEXOEV
0RGXOHVWREHIRUPHG
0RWRU0RGXOHLQWHUIDFH
Figure 10-2 Motor Module interface
Procedure
Before you form the DC link capacitors, the DC link bridge must be removed.
It is not permissible that the drive unit receives a power-on command (e.g. from the
keyboard, BOP20 or terminal strip).
Connect the forming circuit.
During the forming process, the incandescent lamps must become less bright or go
completely dark. If the incandescent lamps continue to be brightly lit, a fault has occurred
in the drive unit or in the wiring.
10.4 10.4 Spare parts
For a list of spare parts, see:
http://support.automation.siemens.com/WW/view/de/16612315