Line Modules Booksize
3.8 Smart Line Modules (5 kW und 10 kW) with external air cooling
Booksize power units
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
299
3.8.3.3 X1 line connection
Table 3-60 Terminal block X1 of Smart Line Module (5 kW and 10 kW)
Terminal Technical specifications
U1
V1
W1
Supply voltage:
380 V - 480 V 3 AC, 50/60 Hz
Max. connectable cross-section: 6 mm
2
Type: Screw terminal 5 (see Connection System)
Tightening torque: 1.2 - 1.5 Nm
PE connection Threaded hole M5/3 Nm
1)
1)
for ring terminal end in accordance with DIN 46234