Line Connection Booksize
2.13 Line connection variants
Booksize power units
136 Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
2.13.3.8 Assignment of isolating transformers to Active Line Modules
Table 2-50 Matching transformers with isolated windings for 50/60 Hz supply systems
Active Line Module
16 kW 36 kW 55 kW 80 kW 120 kW
Rated power [kVA] 21 47 70 104 155
Power loss, max. [W] 650 1200 2020 2650 3050
Vector group Yyn0
Degree of protection acc. to
DIN EN 60529 (IEC 60529)
Degree of protection IP00: _ → Order No. 0
Humidity rating in accordance with DIN
EN 60721-3-3
Cl. 3K5, Condensation and icing excluded
Low air temperature 0 °C (+32 °F)
Permiss. ambient temperature
Operation [°C]
-25 to +40, for power de-rating up to +55, ISOKL: H, t
a
= 40
Approx. weight for
degree of protection IP00
120
200
300
425
600
Max. conn., secondary [mm
2
] 16 35 70 Cable lug according to DIN 46235
Input voltage, 3-ph. 575 V AC - 500 V AC - 480 V AC ± 10%; 50 Hz - 5% to 60 Hz + 5%
Rated input current [A] 26 58 87 127 189
Max. conn., primary [mm
2
] 16 35 50 70 Cable lug acc. to
DIN 46235
Short-circuit voltage uk [%] 2.49 2.64 2.41 2.26 2.05
Order No. 4BU4395-
0SA7_-0C
4BU4795-
0SC3_-0C
4BU5595-
0SA4_-0C
4BU5895-
0SA6_-0C
4BU6095-
0SA6_-0C
Input voltage, 3-ph. 440 V AC - 415 V AC - 400 V AC ± 10%; 50 Hz - 5% to 60 Hz + 5%
Rated input current [A] 31 69.5 104 154 228
Max. conn., primary [mm
2
] 16 35 70 70 Cable lug acc. to
DIN 46235
Short-circuit voltage uk [%] 2.47 2.63 2.4 2.24 2.09
Order No. 4BU4395-
0SA8_-0C
4BU4795-
0SC4_-0C
4BU5595-
0SA5_-0C
4BU5895-
0SA7_-0C
4BU6095-
0SA7_-0C
Input voltage, 3-ph. 240 V AC - 220 V AC - 200 V AC ± 10%; 50 Hz - 5% to 60 Hz + 5%
Rated input current [A] 62 138.5 210 309 450
Max. conn., primary [mm
2
] 35 70 Cable lug according to DIN 46235
Short-circuit voltage uk [%] 2.43 2.59 2.61 2.2 2.16
Order No. 4BU4395-
0SB0_-0C
4BU4795-
0SC5_-0C
4BU5595-
0SA6_-0C
4BU5895-
0SA8_-0C
4BU6095-
0SA8_-0C