Motor Modules Booksize
4.2 Motor Modules with internal air cooling
Booksize power units
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
337
4.2.7 Technical data
Table 4-10 Technical data for Booksize Single Motor Modules (3 to 30 A)
Internal air cooling 6SL3120– 1TE13-
0AAx
1TE15-
0AAx
1TE21–
0AAx
1TE21–
8AAx
1TE23-
0AAx
Rated current A 3 5 9 18 30
Voltage
Infeed:
DC link voltage
Electronics power supply
V
DC
V
DC
510 – 720
24 (20.4 - 28.8)
Output voltage V
ACrms
0 - 0.717 x DC link voltage
Overvoltage trip threshold
Undervoltage trip threshold
V
DC
V
DC
820 ± 2 %
380 ± 2 %
Electronics current consumption at 24 V A
DC
0.85 0.85 0.85 0.85 0.9
Total power loss
(including electronic losses)
1)
W 50.4 75.4 100.4 185.4 311.6
Rated output current (l
n
) A
ACrms
3 5 9 18 30
Base load current (I
base
) A 2.6 4.3 7.7 15.3 25.5
Intermittent duty current (l
s6
) 40 % A
ACrms
3.5 6 10 24 40
Peak current (l
max
) A
ACrms
6 10 18 36 56
DC link busbar current carrying capacity A
DC
100 100 100 100 100
24 V busbar current carrying capacity A
DC
20 20 20 20 20
Rated power
(with DC link voltage of 600 V
DC
and pulse
frequency of 4 kHz)
kW 1.6 2.7 4.8 9.7 16
Max. pulse frequency without derating kHz 4 4 4 4 4
Max. pulse frequency with derating kHz 16 16 16 16 16
Max. ambient temperature without derating °C 40 40 40 40 40
Max. ambient temperature with derating °C 55 55 55 55 55
DC link capacitance μF 110 110 110 220 705
Sound pressure level dB(A) <60 <60 <60 <60 <60
Cooling type Internal
fan
Internal
fan
Internal
fan
Internal
fan
Internal
fan
Cooling air requirement m
3
/h 29.6 29.6 29.6 29.6 56
Weight kg 5 5 5 5 6.9
1)
For an overview, see the power loss tables in Chapter Cabinet design