2.13.3.11 Technical specifications of the transformers
Basic reference conditions under which the transformers can be loaded with the rated
power P
n
indicated in the selection tables:
Continuous operation P
n
Frequency 50 Hz to 60 Hz
Degree of protection IP00
Installation altitude up to 1000 m above sea level
Rated ambient temperature t
a
Installation and operating conditions that deviate from these values, influence the
permissible continuous loads. For example, a lower ambient temperature of 30 °C enables
a higher utilization.
       





3
Q
3
QSHUPLVV
$PELHQWWHPSHUDWXUHr&
W
D
r&+
W
D
r&%
W
D
r&+
Figure 2-52 Load characteristics in relation to the ambient temperature





3
Q
3
QSHUPLVV
,QVWDOODWLRQDOWLWXGH>[PDERYHVHDOHYHO@
Figure 2-53 Load characteristics in relation to the installation altitude
The mentioned transformers have a neutral point that can be loaded with 10%. They are
mainly designed for secondary-side symmetrical supply systems.