Line Connection Booksize   
2.13 Line connection variants 
  Booksize power units 
130  Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6 
2.13.3.5  Assignment of autotransformers to Smart Line Modules 
Table 2-46  Autotransformers for 480/440 V input voltage 
  Smart Line Module 
  5 kW /10 kW /16 kW  36 kW 
Rated power [kVA] 
Autotransformer IP00 
 
21 
 
46.5 
Input voltage [V]  480/440 V AC 3-phase ± 10%; 50 Hz - 5% to 60 Hz + 5% 
Output voltage [V]  400 V AC, 3-phase 
Vector group  Yna0 
Permiss. ambient temperature 
Operation [°C] 
 
-25 to +40, for power de-rating up to +55 °C, ISOKL: H, t
a
 = 40 
Humidity rating in accordance with DIN 
EN 60721-3-3 
Cl. 3K5, Condensation and icing excluded 
Low air temperature 0 °C (+32 °F) 
Degree of protection to EN 60529 
(IEC 60529) IP00 
Degree of protection IP00: _ → Order No. A 
Order No.   4AP2796-0EL40-2X_0  4AU3696-0ER20-2X_0 
Power loss [W] 
Autotransformer IP00 
 
160 
 
430 
Short-circuit voltage uk [%]  ≤ 1.5 
Conn. cross-section, max. 
primary/secondary sides  
16 mm
2
  35 mm
2
 
Fuse, primary side  35 A gL  80A gL 
Weight [kg], approx. for 
Degree of protection IP00 
 
29 
 
52 
Terminal arrangement   1U1/1U3/1V1/1V3/1W1/1W3/2U1/2V1/2W1/N 
  1U1 to 1W1 = 480 V input, 1U3 to 1W3 = 440 V input,  
2U1 to 2W1 = 400 V output, N = neutral point