Line Modules Booksize
3.3 Active Line Modules with external air cooling
Booksize power units
194 Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
NOTICE
The 24 V terminal adapter may only be withdrawn vertically to the front panel (i.e. not at an
angle)!
3.3.7 Technical data
Table 3-21 Technical data for Active Line Modules with external air cooling, part 1
Internal air cooling 6SL3131– 7TE21–6AAx 7TE23–6AAx 7TE25–5AAx 7TE25–5AA3
+ Active
Interface
Module
Rated power kW 16 36 55 55
Infeed:
Rated power (S1)
1)
Infeed power (S6-40%)
1)
Peak infeed power
1)
kW (Pn)
kW (Ps6)
kW (Pmax)
16
21
35
36
47
70
55
71
91
55
71
110
Regenerative feedback:
Continuous regenerative power rating
Peak regenerative power rating
kW
kW
16
35
36
70
55
91
55
110
Line supply voltages:
Line voltage
Line frequency
Electronics power supply
V
ACrms
Hz
V
DC
3-ph. 380 V AC -10% (-15% < 1 min) to 3-ph. 480 V AC +10%
47 to 63 Hz
24 (20.4 - 28.8)
DC link voltage
Overvoltage trip threshold
Undervoltage trip threshold
V
DC
V
DC
V
DC
510 - 720
820 ± 2 %
360 ± 2 %
Rated input current:
at 380 V
AC
at 480 V
AC
/528 V
AC
at 480 V (S6-40%)
Peak current (at 400 V
AC
/480 V
AC
)
A
AC
A
AC
A
AC
A
AC
26
21/19
27
54/45
58
46/42
60
107/89
88
70/64
92
139/116
88
70/64
92
168/140
DC link current:
Rated current
at S6-40%
Peak current
A
DC
A
DC
A
DC
27
35
59
60
79
117
92
121
152
92
121
176
DC link busbar current carrying
capacity
A
DC
100 100 200 200
24 V busbar current carrying capacity A
DC
20 20 20 20
Electronics current consumption A
DC
1.1 1.5 1.9 1.9
Total power loss
(including electronic losses)
2
W 286.4 666 945.6 945.6
Max. ambient temperature without
derating
°C 40 40 40 40
Max. ambient temperature with
derating
°C 55 55 55 55