Line Modules Booksize
3.3 Active Line Modules with external air cooling
Booksize power units
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
195
Internal air cooling 6SL3131– 7TE21–6AAx 7TE23–6AAx 7TE25–5AAx 7TE25–5AA3
+ Active
Interface
Module
Rated power kW 16 36 55 55
DC link capacitance μF 705 1 410 1 880 1 880
Maximum permissible DC link
capacitance
μF 20 000 20 000 20 000 20 000
Power factor cosϕ 1 1 1 1
Circuit-breaker type designation
(status 06/2007)
Rated current
Short-circuit current rating SCCR at
400 V
AC
A
kA
3RV1031-
4FA10
28 ... 40
50
3RV1041-
4LA10
70 ... 90
50
3VL2712-
3DC33-0AA0
125
3VL2712-
3DC33-0AA0
125
Circuit-breaker type designation
(status 07/2007 and later)
Rated current
Short-circuit current rating SCCR at
400 V
AC
Short-circuit current rating SCCR at
480 V
AC
Short-circuit current rating SCCR at
600 V
AC
A
kA
kA
kA
3RV1042-
4FA10
28 ... 40
100
3RV1042-
4LA10
70 ... 90
100
3VL2112-
3KN30-0AA0
125
100
25
3VL2112-
3KN30-0AA0
125
100
25
Circuit-breaker type designation
UL489/CSA C22.2 No. 5-02
Rated current
Rated short circuit current SCCR
A
kA
To be added 3VL2108-
3KN30-0AA0
80
65
3VL2112-
3KN30-0AA0
125
65
3VL2112-
3KN30-0AA0
125
65
UL safety fuse type AJT Class J
Rated current
Short-circuit current rating SCCR at
600 V
AC
A
kA
AJT35
35
200
AJT80
80
200
AJT125
125
200
AJT125
125
200
Safety fuses NH
Rated current
A
3NA3 814
35
3NA3 824
80
3NA3 132
125
3NA3 132
125
Sound pressure level dB(A) <60 <65 <60 <60
Cooling air requirement m
3
/h 56 112 160 160
Rated voltage for rated data 380 V 3 AC
Weight kg 8.78 13.77 18.5 18.5
1)
The specified values apply to 380 V
2)
For an overview, see the power loss tables in Cabinet Design chapter.