Line Modules Booksize   
3.3 Active Line Modules with external air cooling 
  Booksize power units 
196  Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6 
Table 3-22  Technical data for Active Line Modules with external air cooling, part 2 
Internal air cooling  6SL3131–  7TE28–0AAx  7TE31-2AAx 
Rated power  kW  80  120 
Infeed: 
Rated power (S1) 
1) 
Infeed power (S6-40%) 
1) 
Peak infeed power 
1)
 
 
kW (Pn) 
kW (Ps6) 
kW (Pmax) 
 
80 
106 
131 
 
120 
145 
175 
Regenerative feedback: 
Continuous regenerative power rating 
Peak regenerative power rating 
 
kW 
kW 
 
80 
131 
 
120 
175 
Line supply voltages: 
Line voltage 
Line frequency 
Electronics power supply 
 
V
ACrms 
Hz 
V
DC
 
 
3-ph. 380 V AC -10% (-15% < 1 min) to 3-ph. 480 V AC +10% 
47 to 63 Hz 
24 (20.4 - 28.8) 
DC link voltage 
Overvoltage trip threshold 
Undervoltage trip threshold 
V
DC
 
V
DC
 
V
DC
 
510 - 720 
820 ± 2 % 
360 ± 2 % 
Rated input current: 
at 380 V
AC 
at 480 V
AC
/528 V
AC 
at 480 V (S6-40%) 
Peak current (at 400 V
AC
/480 V
AC
) 
 
A
AC 
A
AC 
A
AC
 
A
AC
 
 
128 
102/93 
134 
200/166 
 
192 
152/139 
201 
267/222 
DC link current: 
Rated current 
at S6-40% 
Peak current 
 
A
DC 
A
DC 
A
DC
 
 
134 
176 
218 
 
200 
244 
292 
DC link busbar current carrying 
capacity 
A
DC
  200  200 
24 V busbar current carrying capacity  A
DC
  20  20 
Electronics current consumption  A
DC
 2  2.5 
Total power loss  
(including electronic losses)
2
 
W   1386  2260 
Max. ambient temperature without 
derating 
°C  40  40 
Max. ambient temperature with 
derating 
°C  55  55 
DC link capacitance  μF  2 820  3 995 
Maximum permissible DC link 
capacitance 
μF  20 000  20 000 
Power factor  cosϕ  1  1 
Circuit-breaker type designation 
(status 07/2007 and later) 
Rated current 
Short-circuit current rating SCCR at 
480 V
AC 
Short-circuit current rating SCCR at 
600 V
AC
 
 
 
A 
kA 
 
kA 
 
3VL3117-3KN30-0AA0 
 
175 
100 
 
25 
 
3VL3125-3KN30-0AA0 
 
250 
100 
 
25