Line Modules Booksize
3.3 Active Line Modules with external air cooling
Booksize power units
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
197
Internal air cooling 6SL3131– 7TE28–0AAx 7TE31-2AAx
Rated power kW 80 120
UL safety fuse type AJT Class J
Rated current
Short-circuit current rating SCCR at
600 V
AC
A
kA
AJT175
175
200
AJT250
250
200
Safety fuses NH
Rated current
A
3NA3 136
160
3NA3 144
250
Sound pressure level dB(A) <73 <73
Cooling air requirement m
3
/h 520 520
Rated voltage for rated data 380 V 3 AC
Weight kg 27.66 30.74
1)
The specified values apply to 380 V
2)
For an overview, see the power loss tables in Cabinet Design chapter.
Rated duty cycles of Active Line Modules