Motor-Side Power Components
7.1 Motor reactors
Booksize power units
436 Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
7.1.2 Safety information
WARNING
A ventilation clearance of 100 mm above and below the components must be observed.
Note
The connecting cables to the Motor Module must be kept as short as possible (max. 5 m).
CAUTION
When using motor reactors that SIEMENS has not approved for SINAMICS, then these can
thermally damage the reactor.
CAUTION
The surface temperature of the motor reactors can exceed 80 °C.
CAUTION
The maximum permissible output frequency when motor reactors are used is 120 Hz.