Line Connection Booksize   
2.13 Line connection variants 
  Booksize power units 
122  Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6 
 
From S
K transformer
, the required rated power of the matching transformer can be calculated. 
>N9$@
6
.SODQW
>N9$@ವ6
.OLQH
>N9$@ವXN>@
6
.SODQW
>N9$@6
.OLQH
>N9$@ವ>@
6
Q
 
 
Note 
The system fault level (short-circuit power) at the plant connection S
K plant
 plays a decisive 
role in dimensioning/selecting the matching transformer. 
From the rated power (S
n1
 or S
n2
) calculated under a) and b), the higher value must be 
used for the matching transformer. 
Table 2-43  Transformer configuration instructions 
Used 
Active Line Module P
n
 
Required rated power Sn of 
the isolating/autotransformer 
Required short-circuit 
voltage uk 
Required system fault level 
S
K line
 
16 kW  Sn ≥ 21 kVA  uk ≤ 3%  S
K line
 ≥ 1.12 MVA 
36 kW  Sn ≥ 46 kVA  uk ≤ 3%  S
K line
 ≥ 2.52 MVA 
55 kW  Sn ≥ 70 kVA  uk ≤ 3%  S
K line
 ≥ 3.85 MVA 
80 kW  Sn ≥ 102 kVA  uk ≤ 3%  S
K line
 ≥ 5.6 MVA 
120 kW  Sn ≥ 153 kVA  uk ≤ 3%  S
K line
 ≥ 8.4 MVA 
Used 
Smart Line Module Pn 
Required rated power Sn of 
the isolating/autotransformer 
Required short-circuit 
voltage uk 
Minimum system fault level 
S
K line
 required 
5 kW  Sn ≥ 6.4 kVA  uk ≤ 3%  S
K line
 ≥ 0.35 MVA 
10 kW  Sn ≥ 13 kVA  uk ≤ 3%  S
K line
 ≥ 0.7 MVA 
16 kW  Sn ≥ 21 kVA  uk ≤ 3%  S
K line
 ≥ 1.12 MVA 
36 kW  Sn ≥ 46 kVA  uk ≤ 3%  S
K line
 ≥ 2.52 MVA 
Used Basic Line Module  Required rated power Sn of 
the isolating/autotransformer 
Required short-circuit 
voltage uk 
Minimum system fault level 
S
K line
 required 
20 kW  Sn ≥ 26 kVA  uk ≤ 10%  S
K line
 ≥ 1.4 MVA 
40 kW  Sn ≥ 51 kVA  uk ≤ 10%  S
K line
 ≥ 2.8 MVA 
100 kW  Sn ≥ 127 kVA  uk ≤ 10%  S
K line
 ≥ 7.0 MVA 
 
 
 
Note 
Ask your relevant energy provider for the system fault level S
K line
.