Line Connection Booksize
2.13 Line connection variants
Booksize power units
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
133
Table 2-49 Autotransformers for 220 V input voltage
Basic Line Modules
20 kW 40 kW 100 kW
Rated power [kVA]
Autotransformer IP00
46.5
70.3
155
Input voltage [V] 220 V AC 3-phase ± 10%; 50 Hz - 5% to 60 Hz + 5%
Output voltage [V] 400 V AC, 3-phase
Vector group Yna0
Permiss. ambient temperature
Operation [°C]
-25 to +40, for power de-rating up to +55 °C, ISOKL: H, t
a
= 40
Humidity classification in accordance
with DIN EN 60721-3-3
Cl. 3K5, Condensation and icing excluded
Low air temperature 0 °C (+32 °F)
Degree of protection to DIN EN
60529 (IEC 60529) IP00
Degree of protection IP00: _ --> Order No. 0
Order No. 4BU4395-
0CB6_-8B
4BU4595-
0BD0_-8B
4BU5495-
1AA1_-8B
Power loss [W]
Autotransformer IP00
900
980
1650
Short-circuit voltage uk [%] ≤ 1.5
Conn. cross-section, max.
primary/secondary sides
70/50 mm
2
95/70 mm
2
Flat termination
1)
Fuse, primary side 160 A gL 224 A gL 500 A gL
Weight [kg], approx. for
Degree of protection IP00
110
155
310
Terminal arrangement 1U1 to 1W1 = 220 V input, 2U1 to 2W1 = 400 V output, N = neutral point
1)
FL = flat-type terminal, drill hole Ø 9 mm