Line Modules Booksize
3.2 Active Line Modules with internal air cooling
Booksize power units
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
169
Table 3-11 Technical data of Active Line Modules
Internal air cooling 6SL3130– 7TE28–0AAx 7TE31–2AAx
Rated power kW 80 120
Infeed:
Rated power (S1)
1)
Infeed power (S6-40%)
1)
Peak infeed power
1)
kW (Pn)
kW (Ps6)
kW (Pmax)
80
106
131
120
145
175
Regenerative feedback:
Continuous regenerative power
rating
Peak regenerative power rating
kW
kW
80
131
120
175
Line supply voltages:
Line voltage
Line frequency
Electronics power supply
V
ACrms
Hz
V
DC
380 3 AC -10% (-15% < 1 min) to 480 3 AC +10%
47 to 63
24 (20.4 - 28.8)
DC link voltage
Overvoltage trip threshold
Undervoltage trip threshold
V
DC
V
DC
V
DC
510 - 720
820 ± 2%
360 ± 2%
Rated input current:
at 380 V
AC
at 480 V
AC
/528 V
AC
at 480 V; S6-40%)
Peak current (at 400 V
AC
/480 V
AC
)
A
AC
A
AC
A
AC
A
AC
128
102/93
134
200/166
192
152/139
201
267/222
DC link current:
Rated current
at S6-40%
Peak current
A
DC
A
DC
A
DC
134
176
218
200
244
292
DC link busbar current carrying
capacity
A
DC
200 200
24 V busbar current carrying capacity A
DC
20 20
Electronics current consumption A
DC
2 2.5
Total power loss
(including electronic losses)
2)
W 1386 2260
Max. ambient temperature
without derating
°C 40 40
Max. ambient temperature
with derating
°C 55 55
DC link capacitance μF 2 820 3 995
Maximum permissible DC link
capacitance
μF 20 000 20 000
Power factor cosϕ 1 1
Circuit-breaker type designation
UL489/CSA C22.2 No. 5-02
(status 07/2007 and later)
Rated current
Short-circuit current rating SCCR at
480 V
AC
Short-circuit current rating SCCR at
600 V
AC
A
kA
kA
3VL3117-3KN30-0AA0
175
100
25
3VL3125-3KN30-0AA0
250
100
25