8.1 Shield connecting plates
Booksize power units
458 Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
Table 8-5 Electrical connection at the shield connecting plate for 200 mm component using as an example, internal air
cooling
Unlock and remove the cover of the
terminal block.
Remove nuts M8 using a suitable tool Secure the earthing cable with
screwdriver T25 and the power cable
with torque spanner M8/13 Nm
Adjust the shock-hazard protection
using a suitable tool
Attach the shock-hazard protection Secure the shield clamp to the shield
connecting plate using a suitable tool
Close the cover of the terminal block.