Line Connection Booksize
2.5 Basic Line Filter for Active Line Modules with Active Interface Module
Booksize power units
48 Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
NOTICE
The associated Line Module must only be connected to the SINAMICS line filter via the
associated line reactor. Additional loads must be connected upstream of the SINAMICS line
filter (if required, via a separate line filter). If this is not observed, other loads could be
damaged or destroyed.
DANGER
The line filters listed conduct a high leakage current via the protective ground conductor.
A permanent PE connection for the line filter or control cabinet is required due to the high
leakage current of the line filters.
Furthermore, the following measures must be taken according to EN 61800-5-1:
Either protective ground conductor cross-sections ≥ 10 mm
2
Cu or installation of a second
protective ground conductor of the same cross-section as the first one.
DANGER
Risk of electric shock. Dangerous voltages are still present for up to 5 minutes after the
power supply has been switched off.
Note
If a high-voltage test is conducted with alternating voltage in the system, the existing line
filters must be disconnected in order to obtain accurate measurements.
CAUTION
Only the line filters described in this Manual must be used. Other line filters can cause line
harmonics that can interfere with or damage other loads powered from the line supply.