Cabinet Design and EMC Booksize   
9.4 Arrangement of components and equipment 
  Booksize power units 
514  Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6 
Arrangement of the Voltage Clamping Module 
 
Line Modules up to 36 kW:  Preferably to the right, next to the Line Module 
Line Modules above 55 kW:  Preferably to the left, next to the Line Module 
When retrofitting:  At the end of the module line-up 
Note concerning the use of components with a width of 50 mm 
 
DANGER 
 
If a 50 mm wide Motor Module or if a DC link component with the appropriate width (e.g. 
Braking Module, Control Supply Module, Voltage Clamping Module) is located at the 
lefthand end of the drive line-up, then the DC link bridge including all of the screws must be 
removed. It is not permissible to insert the screws without a DC link bridge.  
For all other Line Modules and DC link components (e.g. Capacitor Module) that are wider 
than 50 mm, it is not permissible to remove the DC link bridge. 
If this is not carefully observed, this can result in damage and accidents. 
 
 
Figure 9-6  Removing the DC link bridges 
The DC link bridges must be removed by unscrewing the M4 screws.