Cabinet Design and EMC Booksize
9.4 Arrangement of components and equipment
Booksize power units
514 Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
Arrangement of the Voltage Clamping Module
Line Modules up to 36 kW: Preferably to the right, next to the Line Module
Line Modules above 55 kW: Preferably to the left, next to the Line Module
When retrofitting: At the end of the module line-up
Note concerning the use of components with a width of 50 mm
DANGER
If a 50 mm wide Motor Module or if a DC link component with the appropriate width (e.g.
Braking Module, Control Supply Module, Voltage Clamping Module) is located at the
lefthand end of the drive line-up, then the DC link bridge including all of the screws must be
removed. It is not permissible to insert the screws without a DC link bridge.
For all other Line Modules and DC link components (e.g. Capacitor Module) that are wider
than 50 mm, it is not permissible to remove the DC link bridge.
If this is not carefully observed, this can result in damage and accidents.
Figure 9-6 Removing the DC link bridges
The DC link bridges must be removed by unscrewing the M4 screws.