Cabinet Design and EMC Booksize
9.4 Arrangement of components and equipment
Booksize power units
516 Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
The inlet temperature of the air sucked in for cooling the module must not exceed 40°C (with
derating, the inlet temperature must not exceed 55°C). This must be ensured by means of
suitable air guidance, the clearance between the module rows, or by air baffle plates.
The distance between the rows also depends on the required bending radii of the power
cables to be connected.
CAUTION
Signal cables must not be routed parallel to power cables.
Wiring rules for DRIVE-CLiQ
See the Commissioning Manual
Table 9-10 Overview of the DC link rectifier adapter and DC link adapter
Suitable for module width Max. connectable cross-
section
Max. current carrying
capacity
DC link rectifier adapter (cable outlet on top)
6SL3162-2BD00-0AAx 50 mm, 100 mm 10 mm
2
36 A
6SL3162-2BM00-0AAx 150 mm, 200 mm, 300 mm 95 mm
2
240 A
DC link adapter (cable outlet on side)
6SL3162-2BM01-0AAx all 95 mm
2
240 A
Note
The current carrying capacity of the DC link busbars must be taken into account. For the
specifications, see the technical data for the components.