Table 9-16 Connectable cable cross-sections: Power supply cable/motor cable, part 2
Connection cross-section [mm
2
]
Component Terminal type 25 35 50 70 95 120
Motor Module
3 A to 30 A
2 x 3 A to 2 x 18 A
Motor connector 30 A 3+2 pin
Motor Module
45 A to 60 A
Threaded bolt M6/6 Nm
1)
X X X
Motor Module 85 A Threaded bolt M8/13 Nm X X X X X X
Motor Module
132 A to 200 A
Threaded bolt M8/13 Nm X X X X X X
Smart Line Module
5 kW to 10 kW
Screw terminal
Acitve Line Module 16 kW
Smart Line Module 16 kW
Screw terminal
Acitve Line Module 36 kW
Smart Line Module 36 kW
Threaded bolt M6/6 Nm X X X
Acitve Line Module 55 kW Threaded bolt M8/13 Nm X X X X X X
Active Line Module
80 kW to 120 kW
Threaded bolt M8/13 Nm X X X X X X
1)
for ring cable lug to DIN 46234
Terminal area for flexible cable with wire end ferrule
Terminal area for flexible cable with ring cable lug M6
Terminal area for flexible cable with ring cable lug M8
IP2xB to EN 60529 ensured; note: the shock-hazard protection installed as standard must be used or adjusted as appropriate.
Table 9-17 Connectable cable cross-sections: Power supply cable/connection for braking resistor, part 3
Connection cross-section [mm
2
]
Component Terminal type 1.5 2.5 4 6 10 16
Basic Line Module 20 kW
line connection
Screw terminal x x x x x x
Basic Line Module 20 kW
Connection for braking
resistor
Screw terminal x x x
Basic Line Module 40 kW
line connection
Screw terminal x x
Basic Line Module 40 kW
Connection for braking
resistor
Screw terminal x x x x
Basic Line Module 100 kW
line connection
Threaded bolt
M8/13 Nm
x x x x x