10.2 Operating the control panel in STARTER (with the motor rotating)
Creating a Drive Project
10-146
SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition
6FC5 397-0CP10-1BA0
Table 10-1 Control word for the sequence control
Signal (control
panel)
PROFIdrive
bit no. in CTW
sequence control
Meaning
ON/OFF1 Bit 0 0 = OFF (OFF1), stop via ramp-function generator, followed by pulse
block
1 = ON, service condition
ON/OFF2 Bit 1 0 = Coast down (OFF2), pulse block, motor coasts to standstill
1 = Do not coast down, operating condition
ON/OFF3 Bit 2 0 = Rapid stop (OFF3)
1 = No rapid stop, service condition
Pulse enable Bit 3 0 = Disable operation, pulse suppression
1 = Enable operation, enable pulses
Enable ramp-
function gene-
rator
Bit 4 0 = Set ramp-function generator to 0
1 = Enable ramp-function generator
Start/stop
ramp-function
generator
Bit 5 0 = Freeze ramp-function generator, retain current output value
1 = Re-enable ramp-function generator; will follow the input value
Setpoint
enable
Bit 6 1 = Enable setpoint
0 = Inhibit setpoint and set to 0
Click the
Enables field.
Fig. 10-36 Enables
5. As shown in Fig. 10-36, click the Enables field to set the commands for enabling the
control words in the drive system.
Click
Infeed control priority.
Fig. 10-37 Incoming supply control priority
6. Click Infeed control priority. The supply (Active Line Module) is turned on.
7. Before starting the motor by choosing Motor on (see Fig. 10-38), you have to make the
following settings: