VAP416 Installation & Operation Manual
TD-1/07-004
45 / 81
Factory default: All selected
Example: To set reset permission as default value do
10 06 1 (turn on) 2 (turn on) √
8.2.1.6. AC Fail Call Delay
Panel doesn’t dial Central Monitoring Station or User during time entered this
address when AC voltage of panel is off.
Address 10 08. < IP >
Display for settings:
LED 10 08 (wait)
LCD PANEL SETTINGS→GENERAL SETTINGS→POWER REPORT DLY (wait)
Change for settings:
LED 10 08 <Time> "√"
LCD PANEL SETTINGS→GENERAL SETTINGS→POWER REPORT DLY
<Time> "√"
Shown/Entered value: <Time>, Value between 1...255 as minute
Factory default: 15
Example: To set delay time as 30 minutes do
10 08 3 0
8.2.1.7. Double Hit or Cross Zone Timer
Cross zone timer starts when zone trip occurs. First trip on a cross zone will not
cause an alarm. If a second cross zone that is on the same partition (or the same
zone if double hit feature is enabled) is violated within Cross zone timer duration, the
panel goes into alarm and sends both zone alarms and "Intrusion Verifier" code to
Central Monitoring Station(*) "Cross Zone Fault" code is sent to Central Monitoring
Station(*) if no any other violation after first trip on cross zones that are on the same
partition occurs within Cross zone timer duration.
Note: Don’t forget that codes can be sent to Central Monitoring Station if it is not
disabled by installer
Address 10 09. < IP >
Display for settings:
LED 10 09 (wait)
LCD PANEL SETTINGS→GENERAL SETTINGS→CROSS ZONE (wait)
Change for settings:
LED 10 09 <Süre> "√"
LCD PANEL SETTINGS→GENERAL SETTINGS→CROSS ZONE
<Time> SECOND "√"
Shown/Entered value: <Time>, Value between 0...255 as second
Factory default: 60
Example: To set cross zone time as 42 second
10 09 4 2
8.2.2. Siren Settings
8.2.2.1 Siren Partitions
Siren doesn’t alarm if alarm comes from unselected siren partition;
ABCD: 1.option=A, 2.option=B, 3.option=C, 4. option=D
SPT: 1.option=Interior, 2.option=Window, 3.option=Door, 4.option=Exterior