If it is used with SPT, only 1=Interior is recommended setting. Page 30 for
the details.
Address 11 01. < IP >
Display for settings:
LED 11 01 (wait)
LCD PANEL SETTINGS→SIREN SETTINGS→SIREN (wait)
Change for settings:
LED 11 01 <Value> "√"
LCD PANEL SETTINGS→SIREN SETTINGS→SIREN
PARTITIONS: <Value> "√"
Shown/Entered value: <Value>, 1,2,3,4 multi selection from above list
Factory default: All selected
Example: Sounding the siren when alarm generates A and B
11 01 1 (turn on) 2 (turn on) √
8.2.2.2 Siren Cut off Time
Address 11 02. < IP >
Display for settings:
LED 11 02 (wait)
LCD PANEL SETTINGS→SIREN SETTINGS→CUT OFF TIME (wait)
Change for settings:
LED 11 02 <Time> "√"
LCD PANEL SETTINGS→SIREN SETTINGS→CUT OFF TIME
<Time> MINUTE "√"
Shown/Entered value: <Time>, Value between 0...255 as minute
Factory default: 3 minute
Note: Contact continuously if 0 is entered.
Example: Contact continuously if 0 is entered
11 02 1 2 √
8.2.3. Automatic Arm/Disarm Settings
Panel can automatically arm/disarm panel in specific time of day.
8.2.3.1 Automatic Arm Partitions
Automatic Arm Partition Selection
Selected partitions in this address are automatically armed. To disable automatic arm
feature, unselect partitions. Meanings of options are in the following;
ABCD: 1.option=A, 2.option=B, 3.option=C, 4. option=D
SPT: 1.option=Interior, 2.option=Window, 3.option=Door, 4.option=Exterior
If it is used with SPT, only 1=Interior is recommended setting. Page 30 for
the details.
Address 12 01. < IP >
Display for settings:
LED 12 01 (wait)
LCD PANEL SETTINGS→AUTO ARM/DISARM→AUTO ARM (wait)
PARTITIONS:
Change for settings:
LED 12 01 <Value> "√"
LCD PANEL SETTINGS→AUTO ARM/DISARM→AUTO ARM
PARTITIONS: <Value> "√"