8.6.2. Dial Attempt
Address 50 02. < IP >
Display for settings:
LED 50 02 (wait)
LCD COMMUNICATOR→GENERAL SETTINGS→DIAL ATTEMPTS (wait)
Change for settings:
LED 50 02 <Value> "√"
LCD COMMUNICATOR→GENERAL SETTINGS→DIAL ATTEMPTS
<Value>
Shown/Entered value: <Value>, Value between 1...15 as number.
Factory default: 3
Example: To set dial attempt to 5 do.
50 02 5 √
8.6.3. Central Monitoring Station Answer Wait Time
Address 50 03. < IP >
Display for settings:
LED 50 03 (wait)
LCD COMMUNICATOR→GENERAL SETTINGS→ANSWER WAIT TIME (wait)
Change for settings:
LED 50 03 <Value> "√"
LCD COMMUNICATOR→GENERAL SETTINGS→ANSWER WAIT TIME
<Value> SECOND
Shown/Entered value: <Value>, Value between 10...60 as second
Factory default: 30 second
Example: To set time to 45 seconds do.
50 03 4 5 √
8.6.4. Periodic Test Report Range
Address 50 04. < IP >
Display for settings:
LED 50 04 (wait)
LCD COMMUNICATOR→GENERAL SETTINGS→TEST INTERVAL (wait)
Change for settings:
LED 50 04 <Value> "√"
LCD COMMUNICATOR→GENERAL SETTINGS→TEST INTERVAL
<Value> HOUR
Shown/Entered value: <Value>, Value between 1...48 as hour
Factory default: 24 hour
Example: To set periodic test report interval to 6 hours do.
50 04 6 √
8.6.5. First Test Report Time
The test report are periodically sent to central monitor station after the time which
was adjusted in this address. The first test report timing is updated if a value is
entered the addresses of test report event sending or periodically test report range.
Address 50 05 < IP >
Display for settings:
LED 50 05 (wait)
LCD COMMUNICATOR→GENERAL SETTINGS→FIRST TEST AT (wait)