Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
Page 100/226 © Woodward
Menu 7 Electrical Parameters
This menu contains the electrical parameters of the DSLC-2.
Figure 3-31: ToolKit electrical parameters
Menu 7 provides all the AC measurement, voltage, current, power and reactive power. The generator is always a
3-phase measurement and the busbar is measured as a single phase. A configuration in Menu 5, Auxiliary busbar
available (parameter 7629), allows additionally the measurement of the busbar with 3 phases. The option of the
3-phase busbar measurement allows the monitoring of all 3 phases and detection of the busbars phase rotation.
Menu 7 will display the auxiliary busbar measurement values when parameter 7629 is configured toYes”.
ID
Parameter
CL
Setting range
Format
Description
135
Generator
total power
-
Info
0.0 kW
Display of Generator total power in kW.
4622
Generator
active power
-
Info
0 %
Display of Generator active power in %.
137
Generator
apparent
power
- Info 0.0 kVA Display of Generator apparent power in kVA.
136
Generator
reactive
power
-
Info
0 kvar
Display of Generator reactive power in kvar.
160
Generator
power factor
-
Info
1.00
Display of Generator power factor.
Only shown, if
auxiliary busbar is enabled
(parameter 7629)