Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
Page 150/226 © Woodward
Low Voltage System 600 V / 346 V - 3-Phase with Neutral
Phase rotation clockwise
Generator measurement: 3-Phase PT “wye” (Phase L2 (B) is grounded at the DSLC-2 connection)
Busbar measurement: 1-Phase PT L1-N (“Phase neutral”)
Figure 4-9: Low voltage system 600 V / 346 V – 3-phase with neutral
Configuration
Measurement
Voltage Monitoring
Menu 5
Generator rated voltage (parameter 1766): “600 V”
Generator current input (parameter 1850): “L1 L2 L3”
Generator voltage measuring (parameter 1851): “3Ph 4W”
Busbar rated voltage (parameter 1781): “346 V”
1Ph2W voltage input (parameter 1858): “Phase neutral
1Ph2W phase rotation (parameter 1859): “CW”
Auxiliary busbar available (parameter 7629): “No”
Transformer
Gen. PT primary rated voltage (parameter 1801): “600 V”
Gen. PT secondary rated volt. (parameter 1800): “120 V”
Bus PT primary rated voltage (parameter 1804): “600 V”
Bus PT secondary rated volt. (parameter 1803): “120 V”
Gen [V] L1-L2
Gen [V] L2-L3
Gen [V] L3-L1
Gen [A] L1
Gen [A] L2
Gen [A] L3
Gen [kW]
Gen [KVA]
Gen [kvar]
Gen [PF] L1
Gen [PF] L2
Gen [PF] L3
Gen [Hz]
Gen Phase rotation
Bus [V] L1
Bus [Hz]
Phase-Angle
Bus-Gen
Gen [V] L1-L2
Gen [V] L2-L3
Gen [V] L3-L1
Table 4-8: Low voltage system 600 V / 346 V – 3-phase with neutral