Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
Page 30/226 © Woodward
Voltage Measuring: Generator, Parameter Setting '3Ph 3W' (3-phase, 3-wire)
Figure 2-13: Voltage measuring - generator windings, 3Ph 3W
Figure 2-14: Voltage measuring - generator measuring inputs, 3Ph 3W
3Ph 3W
Wiring terminals
Note
Rated voltage (range) [1] 120 V (50 to 130 V
eff.
) [4] 480 V (131 to 480 V
eff.
)
3
Measuring range (max.)
[1] 0 to 150 Vac
[4] 0 to 600 Vac
Figure
A
C
E
G
B
D
F
H
DSCL-2 terminal 29 31 33 35 30 32 34 36
Phase
L1 / AØ
L2 / BØ
L3 / CØ
---
L1 / AØ
L2 / BØ
L3 / CØ
---
Table 2-6: Voltage measuring - terminal assignment - generator, 3Ph 3W
3 For different voltage systems, different wiring terminals have to be used.
L1
L2
L3
B2
C2
C1
A1
A2
B1
A
B
C
L1
L2
L3
B1B2
C6
C5
A1
A2
B5B6
A
B
C
C2
C1
A5
A6