Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
© Woodward Page 25/226
Power Supply
WARNING – Protective Earth
Protective Earth (PE) must be connected to the unit to avoid the risk of electric shock. The conductor
providing the connection must have a wire larger than or equal to 2.5 mm² (14 AWG). The connection
must be performed properly.
Please use the protective earth connection at the sheet metal housing (refer to Figure 2-1 on page 19).
Table 2-2: Power supply - terminal assignment
Figure 2-7: Power supply - crank waveform at maximum load
Woodward recommends to use one of the following slow-acting protective devices in the supply line to
terminal 63:
• Fuse NEOZED D01 6A or equivalent
or
•
Miniature Circuit Breaker 6A / Type C (for example: ABB type: S271C6 or equivalent)