Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
© Woodward Page 101/226
ID
Parameter
CL
Setting range
Format
Description
139
Generator
power factor
L1
-
Info
1.00
Display of
Generator power factor L1
.
203
Generator
power factor
L2
-
Info
1.00
Display of Generator power factor L2.
204
Generator
power factor
L3
-
Info
1.00
Display of Generator power factor L3.
144
Generator
frequency
-
Info
0.00 Hz
Display of Generator frequency in Hz.
209
Busbar
frequency
-
Info
0.00 Hz
Display of
Busbar frequency
in Hz.
216
Busbar
average volt
-
Info
0.0 V
Display of Busbar average voltage in V.
181
Phase angle
busbar - ge-
nerator
- Info 180.0° Display of Phase angle busbar-generator in degrees.
4640
Delta
frequency
busbar - ge-
nerator
-
Info
0.00 Hz
Display of Delta frequency busbar-generator in Hz.
114
Generator
voltage L1-N
-
Info
0.0 V
Display of
Generator voltage L1-N
in V.
115
Generator
voltage L2-N
-
Info
0.0 V
Display of Generator voltage L2-N in V.
116
Generator
voltage L3-N
- Info
0.0 V Display of Generator voltage L3-N in V.
108
Gen. Voltage
L1-L2
-
Info
0.0 V
Display of Generator voltage L1-L2 in V.
109
Gen. Voltage
L2-L3
-
Info
0.0 V
Display of Generator voltage L2-L3 in V.
110
Gen. Voltage
L3-L1
-
Info
0.0 V
Display of
Generator voltage L3-L1
in V.
4152
Generator
phase
rotation
-
Info
- / CW /
CCW
Display of Generator phase rotation:
-: The phase rotation is not measurable
CW: Clock Wise = phase rotation right
CCW:
Counter Clock Wise = phase rotation left
111
Generator
current L1
-
Info
0.0 A
Display of Generator current L1 in A.
112
Generator
current L2
- Info
0.0 A Display of Generator current L2 in A.
113
Generator
current L3
-
Info
0.0 A
Display of Generator current L3 in A.
4152
Configured
busbar
phase rota-
tion
-
Info
CW /
CCW
Display of the Configured busbar phase rotation:
CW: Clock Wise = phase rotation right
CCW: Counter Clock Wise = phase rotation left
NOTE: This is no measurement displaying. This field shows the
configuration of the 1Ph 2W phase rotation (parameter 1859) in
Menu 5.

Table of Contents