Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
© Woodward Page 85/226
Modbus Interface Definitions
The unit offers a Modbus address table with for visualizing systems. The table contains 16 bit integer (short) and
32 bit integer (long) variables. The contents of some measurement long variables are also available as short va-
riables. To cover all measurement ranges in a satisfying resolution, the engineering unit Watt, Voltand
Amperecan be adjusted according to the application.
ID
Parameter
CL
Setting range
Default
Description
3181
Power [W]
exponent
10^x
2 2 to 5 3 This setting adjusts the format of the 16 bit power values in the
data telegram.
Example power measurement:
The measurement range is 0 to 250 kW.
Momentarily measurement value = 198.5 kW (198,500 W)
Setting
Meaning
Calcula-
tion
Transfer
value
(16Bit,
max.
32767)
Possible
Display
Format
2 10
2
198500 𝑊
10
2
𝑊
1985 198.5 kW
3 10
3
198500 𝑊
10
3
𝑊
198 198 kW
4 10
4
198500 𝑊
10
4
𝑊
19 N/A
5 10
5
198500 𝑊
10
5
𝑊
1 N/A
3182
Volts [V]
exponent
10^x
2
-1 to 2
0
This setting adjusts the format of the 16 bit voltage values in the
data telegram.
Example voltage measurement:
The measurement range is 0 to 480 V.
Momentarily measurement value = 477.8 V
Setting
Meaning
Calcula-
tion
Transfer
value
(16Bit,
max.
32767)
Possible
Display
Format
-1 10
-1
477.8 𝑉
10
−1
𝑉
4778 477.8 V
0 10
0
477.8 𝑉
10
0
𝑉
477 477 V
1 10
1
477.8 𝑉
10
1
𝑉
47 N/A
2 10
2
477.8 𝑉
10
2
𝑉
4 N/A
3183
Current [A]
exponent
10^x
2
-1 to 0
0
This setting adjusts the format of the 16 bit current values in the
data telegram.
Example current measurement:
The measurement range is 0 to 500 A.
Momentarily measurement value = 345.4 A
Setting
Meaning
Calcula-
tion
Transfer
value
(16Bit,
max.
32767)
Possible
Display
Format
-1 10
-1
345.4 𝐴
10
−1
𝑉
3454 345.4 A
0 10
0
345.4 𝑉
10
0
𝑉
345 345 A
Table 3-20: Parameter configuration interfaces