Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
© Woodward Page 119/226
3. Draw the segment numbers into your online diagram (refer to Figure 3-43).
Please consider following rules:
• Begin on the left side with segment number 1.
• The utility and the generators are not segments in sense of the DSLC-2 / MSLC-2 system.
• The segment numbers have to follow a line and shall not branch. (Please refer there for to the chapter
Network/System) for a better understanding.
4. Draw the device numbers of your units in your online diagram (refer to Figure 3-43).
Please consider following rules (for a better overview and understanding):
• The DSLC-2 on the left side should begin with device number 1.
• The DSLC-2s getting device numbers between 1 and 32.
• The MSLC-2 on the left side should begin with device number 33.
• The MSLC-2s getting device numbers between 33 and 48.
5. Draw the “CB Aux” feedbacks and segment connection feedbacks in your online diagram
(refer to Figure 3-43).
Please consider following rules (for a better overview and understanding):
• The DSLC-2 getting usually only their generator breaker feedback.
• The MSLC-2 at the utility breaker getting usually only their utility breaker feedback.
• The MSLC-2 at the tie-breaker getting usually their tie-breaker feedback and parallel the according
segment connector feedback.
Figure 3-43: Example of an online diagram with segment numbers and segment connector feedbacks