Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
© Woodward Page 199/226
In order to reset the default values, parameter 1701 must be enabled.
Example:
The default values are to be reset.
Modbus address = 40000 + (Par. ID + 1) = 41702
Modbus length = 1 (UNSIGNED 16)
The following Modscan32 screenshot shows the settings made to parameter 1701 in ModScan32. It is possible to
set the format to decimal to view the value using the "display options".
Figure 10-12: Modbus - remote control parameter 1701
By double-clicking the address, a Write Register command may be issued. The following screenshot shows how
the parameter is enabled using the ModScan32 Software. The value must be set to "1" to enable the parameter.
Figure 10-13: Modbus - write register - resetting the default values