Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
© Woodward Page 93/226
Linear
2 -100.0 to
100.0 %
0.0 % Process signal input (real value). Linear scaling: This is the per-
centage value according to the lowest hardware signal.
Process signal input (real value). Linear scaling: This is the per-
centage value according to the lowest hardware signal.
This is the resulting percentage value calculated out of the mini-
mum and maximum scaling.
The process control engineering units can be determined here.
With this input the reference and the real value can be defined in
0.0 This value is the engineering unit value to the percentage value
according to the lowest hardware signal (parameter 4322).
This value is the engineering unit value to the percentage value
according to the highest hardware signal (parameter 4323).
This is the resulting process signal input value calculated out of
the minimum and maximum scaling, adjusted in parameter 7733
Reactive Load Input
This analog input stands for the power factor reference signal. Remote var reference control is not available at
this time. To activate the remote reactive load input, the discret inputs “Voltage raise” and “Voltage lower” must
be closed.
Independent on the setting here the resulting var setpoint for the generator is restricted from +100 % to
-10 % rated reactive power, when in base load mode, process mode or there is an active MSLC-2. Re-
striction is not active in isochronous or load sharing modes.
Figure 3-28: ToolKit – reactive load input
7713
HW signal
2 0 to 20 mA./
4 to 20 mA./
0 to 10 V./
0 to 5 V./
1 to 5 V Selection of hardware signal range.