Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
© Woodward Page 93/226
Linear
ID
Parameter
CL
Setting range
Default
Description
4322
User defined
min display
value
2 -100.0 to
100.0 %
0.0 % Process signal input (real value). Linear scaling: This is the per-
centage value according to the lowest hardware signal.
4323
User defined
max display
value
2
0.0 to 100.0 %
100.0 %
Process signal input (real value). Linear scaling: This is the per-
centage value according to the lowest hardware signal.
10151
Process
signal input
-
Info
-
This is the resulting percentage value calculated out of the mini-
mum and maximum scaling.
7732
Process
engineering
unit
2
kW / °C / kPA /
bar / V / mA
kW
The process control engineering units can be determined here.
With this input the reference and the real value can be defined in
engineering units.
7733
Process min
value
2 -999999.9 to
999999.9
0.0 This value is the engineering unit value to the percentage value
according to the lowest hardware signal (parameter 4322).
7734
Process max
value
2
-999999.9 to
999999.9
500.0
This value is the engineering unit value to the percentage value
according to the highest hardware signal (parameter 4323).
7727
Process
signal Input
-
Info
-
This is the resulting process signal input value calculated out of
the minimum and maximum scaling, adjusted in parameter 7733
and 7734.
Reactive Load Input
This analog input stands for the power factor reference signal. Remote var reference control is not available at
this time. To activate the remote reactive load input, the discret inputs “Voltage raise” and “Voltage lower” must
be closed.
NOTE
Independent on the setting here the resulting var setpoint for the generator is restricted from +100 % to
-10 % rated reactive power, when in base load mode, process mode or there is an active MSLC-2. Re-
striction is not active in isochronous or load sharing modes.
Figure 3-28: ToolKit reactive load input
ID
Parameter
CL
Setting range
Default
Description
7713
HW signal
2 0 to 20 mA./
4 to 20 mA./
0 to 10 V./
0 to 5 V./
1 to 5 V
1 to 5 V Selection of hardware signal range.