Prestart Synchronizer Setup
Set all synchronizer (Menu 1) setpoints according to the descriptions above and the work sheet. Leave unknown
values, such as gain and stability, at their default values.
Prestart Load Control Setup
Set all load control (Menu 2) setpoints according to the descriptions above and the work sheet. Proportional load
control mode should be used during initial setup of the DSLC-2 control. Set the unload trip setpoint to approx-
imately 10 % of rated load.
Prestart Process Control Setup
Set all process control (Menu 3) setpoints according to the descriptions above and the work sheet. If gain and sta-
bility values are unknown, leave at their default values.
Prestart Var/Power Factor Control Setup
Set all var/power factor control (Menu 4) setpoints according to the descriptions above and the work sheet. Set
VAR PF control mode to Disableduntil doing the var/PF control adjustment section below.