Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
© Woodward Page 77/226
Menu 5 Configuration
This menu contains system rated frequency, generator rated voltage, PT and CT settings, with operating range
and device number for the configuration of the DSLC-2.
Figure 3-17: ToolKit configuration
General
NOTE
Beside the generator 3-phase measurement the DSLC-2 provides a busbar 1-phase measurements and
an auxiliary busbar 3-phase measurement. The busbar 1-phase measurement at the terminals 37-40
has to be connected in each application. The auxiliary busbar 3-phase AC measurement at the termin-
als 21-28 can additionally be used. When both measurements are used the busbar voltage has to be
connected to both inputs. With the parallel use of the auxiliary busbar measurement, the DSLC-2 can
determine correct voltages on all 3 phases on the bus and becomes part of the operating range- and
the phase rotation monitoring.
ID
Parameter
CL
Setting range
Default
Description
1750
System rated
frequency
2 50 / 60 Hz 60 Hz The rated frequency of the system is used as a reference figure
for all frequency related functions. This is used for operating range
limits, frequency trim reference and frequency monitoring.