Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
© Woodward Page 41/226
Discrete Inputs
Discrete Inputs: Signal Polarity
The discrete inputs are electrically isolated which permits the polarity of the connections to be either positive or
negative.
All discrete inputs must use the same polarity, either positive or negative signals, due to the common
Discrete Inputs: Positive Polarity Signal
Figure 2-27: Discrete inputs - alarm/control input - positive signal
Discrete Inputs: Negative Polarity Signal
Figure 2-28: Discrete inputs - alarm/control input - negative signal
66
GND
com-
mon
ground
67 Discrete input [DI 01] {all} Check 2.5 mm²
68 Discrete input [DI 02] {all} Permissive 2.5 mm²
69 Discrete input [DI 03] {all} Run 2.5 mm²
70 Discrete input [DI 04] {all} CB Aux 2.5 mm²
71 Discrete input [DI 05] {all} Voltage Raise 2.5 mm²
72 Discrete input [DI 06] {all} Voltage Lower 2.5 mm²
73 Discrete input [DI 07] {all} Base Load 2.5 mm²
74 Discrete input [DI 08] {all} Load/Unload 2.5 mm²
75 Discrete input [DI 09] {all} Ramp Pause 2.5 mm²
76 Discrete input [DI 10] {all} Load Raise 2.5 mm²
77 Discrete input [DI 11] {all} Load Lower 2.5 mm²
78 Discrete input [DI 12] {all} Process Control 2.5 mm²
Table 2-17: Discrete input - terminal assignment ½