Figure 10-3: Modbus - sending binary digital orders over interface
ID
Parameter
CL
Setting range
Default
Description
7645
Release
discrete in-
puts over
communica-
tion interface
-
-
-
These single bits control if a function shall be switched by discrete
input or communication interface.
Bit 01 = 1 Check
Bit 02 = 1 Permissive
Bit 03 = 1 Run
Bit 04 = 1 N/A
Bit 05 = 1 Voltage Raise
Bit 06 = 1 Voltage Lower
Bit 07 = 1 Base Load
Bit 08 = 1 Load / Unload
Bit 09 = 1 Ramp Pause
Bit 10 = 1 Load Raise
Bit 11 = 1 Load Lower
Bit 12 = 1 Process
Bit 13 = 1 Droop Tracking
Bit 14 = 1 N/A
Bit 15 = 1 N/A
Bit 16 = 1 N/A
Note:
Bit {x} = 0 -> DI interface = hardware controlled
Bit {x} = 1 -> DI interface = interface controlled