Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
© Woodward Page 113/226
DSLC-2 Overview Page 2
The DSLC-2 overview page 2 informs about the conditions of the DSLC-2 number 17 to 32 connected to the
network. This helps for commissioning a DSLC-2 / MSLC-2 system.
Figure 3-40: ToolKit DSLC-2 overview page 2
ID
Parameter
CL
Setting range
Default
Description
GCB feed-
back
-
Open / Closed
-
This field indicates the GCB state of the DSLC-2 unit 17 to 32.
Sync control
state
- Off /
Check /
Permissive /
Run /
Close Timer /
Sync Timer /
Synchronized /
Auto-Off
- This field indicates the Synchronizer control state of DSLC-2 unit
17 to 32:
Off: The synchronizer is not active.
Check: The synchronizer runs in check mode.
Permissive: The synchronizer runs in permissive mode.
Run: The synchronizer is full active.
Close Timer: This is the GCB close command.
Sync Timer: The synchronizer is stopped, because of a sync
time-out.
Synchronized: The GCB is closed.
Auto-Off: The synchronizer is stopped, because of an unsuccess-
ful closure of the GCB. (resync is disabled).
React. load
control state
- Inactive /
Off /
Droop /
VAR sharing /
Reactive load
control
- This field indicates the Reactive load control state of DSLC-2
unit 17 to 32:
Inactive: The reactive load control mode is inactive.
Off: Var control is generally disabled.
Droop: Droop is active.
VAR sharing: The var sharing is active.
Reactive load control: Var or PF control is active.