EasyManua.ls Logo

Woodward DSLC-2 - Woodward

Woodward DSLC-2
226 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
© Woodward Page 75/226
Voltage Monitoring
ID
Parameter
CL
Setting range
Default
Description
1770
Generator
voltage
monitoring
2 Phase - phase /
Phase - neutral
Phase -
phase
This configuration determines the monitored voltage type.
Phase phase: Only the phase - phase voltages VL12, VL23 and
VL31 are monitored.
Phase neutral: Only the phase - neutral voltages VL1N, VL2N
and VL3N are monitored.
7510
Voltage high
alarm
2
Disabled /
Enabled
Disabled
The Voltage high alarm specifies if the high voltage limit alarm is
activated.
4537
Voltage high
limit
2 0 to 150 % 110 % The Voltage high limit setting specifies the voltage high limit alarm
trip point. The input is related to the rated voltage input configura-
ble in Menu 5 (parameter 1766).
7509
Voltage low
alarm
2
Disabled /
Enabled
Disabled
The Voltage low alarm specifies if the low voltage limit alarm is ac-
tivated.
4536
Voltage low
limit
2
0 to 150 %
90 %
The Voltage low limit specifies the voltage low limit alarm trip
point. The input is related to the rated voltage input configurable in
Menu 5 (parameter 1766).
7511
Voltage
switch
2
Disabled /
Enabled
Enabled
The Voltage switch specifies if the voltage high and low limits will
activate the “High Limit” and “Low Limit” relays.
7512
Voltage
range alarm
2
Disabled /
Enabled
Disabled
Enables or disables the voltage regulator bias output limit alarm.
The alarm voltage range limit will be activated if the limit of the
voltage bias output reaches 100 %.
3pos Controller Voltage
ID
Parameter
CL
Setting range
Default
Description
7515
Three
position
controller
2
Disabled /
Enabled
Disabled
Enabled: The relay outputs “Voltage Raise” and “Voltage Lower
are active. The three position controller will be used with a voltage
regulator that cannot accept the analog voltage bias output.
Disabled: Voltage raise and lower relay contacts are not active.
5650
Voltage ctrl
deadband
1
0.1 to 9.9 %
1.0 %
Isolated operation: The generator voltage is controlled in such a
manner that the measured voltage does not deviate from the con-
figured setpoint by more than the value configured in this parame-
ter without the controller issuing a voltage raise/lower signal to the
voltage regulator. This prevents unneeded wear on the voltage bi-
as output control or the raise/lower relay contacts.
Synchronization: Voltage matching - the generator voltage is
controlled in such a manner that the measured voltage does not
deviate from the monitored reference bus voltage by more than
the value configured in this parameter without the controller is-
suing a voltage raise/lower signal to the voltage regulator. The
value configured for this parameter must be less than the value
configured for the Voltage window for synchronization (parameter
4541).
5651
Time pulse
minimum
1
0.01 to 2.00 s
0.05 s
This is the time the relay output will stay closed when providing a
voltage raise or lower command to the voltage regulator. The
shortest possible pulse time should be configured to limit over-
shoot of the desired voltage reference point.
5652
Gain factor
1
0.1 to 10.0
5.0
The Gain factor influences the operating time of the relays. In-
creasing the Gain factor will increase the response to drive the
voltage within the tolerance for the mode it is in (voltage matching
or voltage control). If the gain is configured too high, the result is
excessive overshoot/undershoot of the desired value.
5653
Expand
deadband
factor
1
1.0 to 9.9
1.0
If the measured generator voltage is within the deadband range
(parameter 5650) and the configured Delay expand deadband
time (parameter 5654) expires, the deadband will be multiplied
with the factor configured here.
5654
Delay
expand
deadband
1
1.0 to 9.9 s
2.0 s
The measured generator voltage must be within the deadband
range for the time configured here in order to multiply the dead
band with the factor configured in parameter 5653.

Table of Contents

Related product manuals