Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
Page 146/226 © Woodward
Low Voltage System 600 V / 346 V - 3-Phase
• Phase rotation clockwise
• Generator measurement: 3-Phase PT “Open Delta” (Phase L2 (B) is grounded at the DSLC-2 connec-
tion)
• Busbar measurement: 1-Phase PT L1-L2 (“Phase – phase”)
Figure 4-5: Low voltage system 600 V / 346 V – 3-phase
• Generator rated voltage (parameter 1766): “600 V”
• Generator current input (parameter 1850): “L1 L2 L3”
• Generator voltage measuring (parameter 1851): “3Ph 4W
OD”
• Busbar rated voltage (parameter 1781): “600 V”
• 1Ph2W voltage input (parameter 1858): “Phase – phase”
• 1Ph2W phase rotation (parameter 1859): “CW”
• Auxiliary busbar available (parameter 7629): “No”
Transformer
• Gen. PT primary rated voltage (parameter 1801): “600 V”
• Gen. PT secondary rated volt. (parameter 1800): “120 V”
• Bus PT primary rated voltage (parameter 1804): “600 V”
• Bus PT secondary rated volt. (parameter 1803): “120 V”