Var control
The var control is active in
Base load control
Process control
With an active MSLC-2 control
Adjustments when in var control
PID var control
o VAR control proportional gain (parameter 5613)
o VAR control integral gain (parameter 5614)
o VAR control derivative ratio (parameter 5615)
The var reference can be changed
Using ToolKit
Voltage raise and lower discrete inputs
Modbus address
Var sharing
The var sharing is active when
PF or var control is selected
Load sharing mode is active
Adjustments for var sharing mode
Var loadshare
o VAR load share gain (parameter 4543)
o VAR load share factor (parameter 4547)
Voltage trim
The voltage trim is active
Isochronous / load sharing mode
Controls at Voltage control setpoint (parameter 5600)
Adjustments for the voltage trim feature
PID voltage trimmer
o Voltage trim proportional gain (parameter 5610)
o Voltage trim integral gain (parameter 5611)
o Voltage trim derivative ratio (parameter 5612)
MSLC-2 is providing PF reference or controlling var or PF across the utility breaker
Adjustments when in PF or var control mode
PID var control
o VAR control proportional gain (parameter 5613)
o VAR control integral gain (parameter 5614)
o VAR control derivative ratio (parameter 5615)
NOTE
If cross-current compensation is installed on the voltage regulator, it must be removed prior to using
the var/PF mode of control or instabilities may result. The droop CTs must remain connected to their
voltage regulator.