B.3 Parameter Table
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 409
7 Accel/decel Ramp Selection 1
Used to switch between accel/decel ramp 1 (set in C1-01, C1-02) and accel/decel ramp 2 (set in C1-03, C1-04).
When combined with another input terminal set for “Accel/Decel ramp 2” (H1- = 1A), the drive can also
switch between accel/decel ramp 3 (set in C1-05, C1-06) and accel/decel ramp 4 (set in C1-07, C1-08).
204
8 Baseblock Command (N.O.)
Closed: No drive output
204
9 Baseblock Command (N.C.)
Open: No drive output
204
F Not Used (Through Mode)
Select this setting when the terminal is not used or when using the terminal in the pass-through mode. The terminal
does not trigger a drive function but can be used as digital input for the controller the drive is connected to.
204
14 Fault Reset
Closed: Resets faults if the cause is cleared and the Up/Down command is removed.
204
15 Fast Stop (N.O.)
Closed: Decelerates to stop at the Fast Stop ramp set to C1-09.
204
16 Motor 2 Selection
Open: Motor 1(E1-, E3-)
Closed: Motor 2 (E2-, E4-)
205
17 Fast Stop (N.C.)
Open: Decelerates to stop at the Fast Stop ramp set to C1-09.
204
18 Timer Function Input
Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction with the timer function output
(H2- = 12).
205
1A Accel/decel Ramp Selection 2
Used in conjunction with an input terminal set for “Accel/decel ramp selection 1” (H1- = 7), and allows the
drive to switch between accel/decel ramp 3 and 4.
206
20 to 2F External Fault
20: N.O., Always detected, ramp to stop
21: N.C., Always detected, ramp to stop
22: N.O., During run, ramp to stop
23: N.C., During run, ramp to stop
24: N.O., Always detected, coast to stop
25: N.C., Always detected, coast to stop
26: N.O., During run, coast to stop
27: N.C., During run, coast to stop
28: N.O., Always detected, Fast Stop
29: N.C., Always detected, Fast Stop
2A: N.O., During run, Fast Stop
2B: N.C., During run, Fast Stop
2C: N.O., Always detected, alarm only (continue running)
2D: N.C., Always detected, alarm only (continue running)
2E: N.O., During run, alarm only (continue running)
2F: N.C., During run, alarm only (continue running)
206
50 Nominal Speed
Closed: Activates the nominal speed (d1-19).
206
51 Intermediate Speed
Closed: Activates the Intermediate Speed (d1-20).
206
52 Releveling Speed
Closed: Activates the Releveling Speed (d1-23).
206
53 Leveling Speed
Closed: Activates the Leveling Speed (d1-26).
207
54 Inspection Operation
Closed: Activates Inspection operation using the speed set in d1-24.
207
55 Rescue Operation
Closed: Activates rescue operation.
207
H1 Multi-Function Digital Input Settings
H1-
Setting
Function Description Page