B.3 Parameter Table
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 413
■ H3: Multi-Function Analog Inputs
No.(Addr.) Name Description Setting Page
H3-01
(410H)
Terminal A1 Signal Level
Selection 0: 0 to 10 V
1: -10 to 10 V
Default: 0
Min: 0
Max: 1
217
H3-02
(434H)
Terminal A1 Function Selection
Sets the function of terminal A1.
Default: 0
Min: 0
Max: 1F
217
H3-03
(411H)
Terminal A1 Gain Setting
Sets the level of the input value selected in H3-02 when 10 V is input at terminal A1.
Default: 100.0%
Min: -999.9%
Max: 999.9%
218
H3-04
(412H)
Terminal A1 Bias Setting
Sets the level of the input value selected in H3-02 when 0 V is input at terminal A1.
Default: 0.0%
Min: -999.9%
Max: 999.9%
218
H3-09
(417H)
Terminal A2 Signal Level
Selection
0: 0 to 10 V
1: -10 to 10 V
Note: Use DIP switch S1 to set input terminal A2 for a current or a voltage input signal.
Default: 0
Min: 0
Max: 0
218
H3-10
(418H)
Terminal A2 Function Selection
Sets the function of terminal A2.
Default: 0
Min: 0
Max: 1F
219
H3-11
(419H)
Terminal A2 Gain Setting
Sets the level of the input value selected in H3-10 when 10 V is input at terminal A2.
Default: 100.0%
Min: -999.9%
Max: 999.9%
219
H3-12
(41AH)
Terminal A2 Bias Setting
Sets the level of the input value selected in H3-10 when 0 V is input at terminal A2.
Default: 0.0%
Min: -999.9%
Max: 999.9%
219
H3-13
(41BH)
Analog Input Filter Time Constant
Sets a primary delay filter time constant for terminals A1 and A2. Used for noise filtering.
Default: 0.03 s
Min: 0.00 s
Max: 2.00 s
219
H3-16
(2F0H)
Offset for Terminal A1
Applies an offset to analog input A1. Can be used for zero adjustment of the analog input.
Default: 0
Min: -500
Max: 500
219
H3-17
(2F1H)
Offset for Terminal A2
Applies an offset to analog input A2. Can be used for zero adjustment of the analog input.
Default: 0
Min: -500
Max: 500
219
H3 Multi-Function Analog Input Settings (H3-02 and H3-10)
Setting
<44> Available in drive software versions PRG: 7017 or later.
Function Description (For when output is 100%) Page
0
Speed Reference Bias
(value added to input signal when multiple
analog terminals supply the speed reference)
E1-04 (maximum output frequency)
220
2
Auxiliary Speed Reference 1
(used as a second speed reference)
E1-04 (maximum output frequency)
220
3
Auxiliary Speed Reference 2
(used as third speed reference)
E1-04 (maximum output frequency)
220
E
<44>
Motor Temperature (PTC thermistor input)
oH3 Alarm detection level: 1.18 V
oH4 Fault detection level: 2.293 V
220
14 Torque Compensation (load cell input)
10 V = Motor rated torque
220
1F Not used (Through Mode)
Sets this value when the terminal is not used or when using the terminal in the pass-through mode.