3BHS212794 E01 REV M ACS6000 USER MANUAL 103/278
05 MECHANICAL INSTALLATION
5.7 Joining busbars
Joining the busbars of two adjoining transport units
Busbar joints within a transport unit have been installed in
the factory.
Use only the supplied installation material.
Orientate the parts of a joint (plates, bolts, and nuts) as shown.
Use a conical spring washer on each side of a connection.
Figure 5-3 Bolted busbar connection
CAUTION
Flashover hazard!
Incorrect orientation of the busbar bolts can cause flashover when the
drive is energized.
Orientate the bolts and the nuts of each connection as shown in this
section to maintain the required minimal distances between
busbars of different polarity.
NOTICE
Risk of component damage!
Tightening torque for M12 bolts:
40 Nm if two busbars are joined
60 Nm if three and more busbars are joined
(1) Conical spring washer
1 1