3BHS212794 E01 REV M ACS6000 USER MANUAL 275/278
10 PREVENTIVE AND CORRECTIVE MAINTENANCE
5. Disconnect the water tubes (1) from the air-to-water heat exchanger,
unplug the cables (2) and remove the fastening screws.
Figure 10-30 Air-to-water heat connections
6. Lift the heat exchanger out of the cabinet.
CAUTIONThe heat exchanger weighs approximately 16 kg and requires
a minimum overhead clearance of 85 cm.
Figure 10-31 Lift heat exchanger out of EXU cabinet
(1) Water tube connections
(1) Fastening screw
(2) Cable connections
1
1