EasyManua.ls Logo

ABB ACS6000 - Cable Tray and Cable Ducts in an LSU (a = Front); Installing the Standard Optical Fibers; Optical Fiber Cables

ABB ACS6000
278 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
06 ELECTRICAL INSTALLATION
3BHS212794 E01 REV M ACS6000 USER MANUAL 132/278
6.4.1 Optical fiber cables
6.4.1.1 Installing the standard optical fibers
1. Pull all cables through the cable duct (3) at the top of the cabinets.
Note: Cut-outs in the ducts provide entry into the cabinets.
Figure 6-5 Cable tray and cable ducts in an LSU (A = front)
2. Lay the cables into their designated trays and cable ducts as
illustrated in Fig. 6-5.
Note: When fastening IGCT power supply cables on the rail for IGCT
power supply cables of RBU, BCU and VLU, make sure that the cables
are at a minimum distance of 5 mm from the closest metal part.
3. Connect all cables and wires according to the Converter
Hardware diagram.
NOTICE
Risk of equipment failure!
Handle optical fibers with care.
- DO NOT touch the ends of the fibers, they are sensitive to dirt.
- When unplugging, hold the connector and not the fiber.
- If an optical fiber is damaged or improperly installed, data
transmission can be affected and the equipment can fail.
- To prevent such problems, follow the handling and
installation guidelines.
Observe the maximum long-term tensile load of 1.0 N and the
minimum bend radius of 25 mm.
(1) Cable tray for auxiliary power
supply cable
(2) Cable tray for control cables
(3) Cable duct for optical fibers
(4) Rail for IGCT power supply cables
of RBU, BCU and VLU
A
1
2
3
4

Table of Contents

Related product manuals