06 ELECTRICAL INSTALLATION
3BHS212794 E01 REV M ACS6000 USER MANUAL 152/278
5. If the outer cable screen is conductive, remove the cable insulation at
the point of entry (1 in Fig. 6-28).
If the outer cable screen is non-conductive:
1. Cut open the cable screen in the middle of the stripped area
(1 in Fig. 6-28).
2. Pull the cable screen ends over the cable insulation to turn the
conductive side inside out (2 in Fig. 6-28).
3. Connect the screens ends with a continuous conducting foil
(3 in Fig. 6-28).
Figure 6-28 Preparing the screens of control cables for EMC plates
(1) Cable screen
(2) Cable screen ends
(3) Conductive foil