3BHS212794 E01 REV M ACS6000 USER MANUAL 151/278
06 ELECTRICAL INSTALLATION
6.8.3 Preparing cables for cable glands
Prepare the cables with an outer cable screen for EMC bonding with the
metal enclosure of the cabinet as illustrated in Fig. 6-26.
Figure 6-27 Preparing auxiliary control cables for cable glands
6.8.4 Preparing cables for EMC plates
1. Remove the grommets from the entry plate.
2. To ensure proper sealing, cut along the marking that corresponds to
the cable diameter.
3. Slide the grommet onto the cable and ensure that the grommet fits
tightly to prevent water from entering the cabinet.
Note: If cables are routed through the cabinet floor, the grommets can
be discarded.
4. If necessary, remove the entry plate and pull the cable through the
entry holes.
(1) Outer cable sheath
(2) Cable gland
(3) Plate
(4) Conductor insulation removed to
expose shield
(5) Conductor screen extension to
connect to PE terminal
1
2
3
4
5