EasyManua.ls Logo

ABB ACS6000 - Initiating an Emergency-Off; Stopping the Drive with the Emergency-Off Function

ABB ACS6000
278 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3BHS212794 E01 REV M ACS6000 USER MANUAL 195/278
08 OPERATION
8.10.2 Stopping the drive with the emergency-off function
The drive is equipped with a hardwired emergency-off circuit. When an
emergency situation occurs during operation, this safety feature ensures
that the drive system can be disconnected without delay from the main
power supply. When the EMERGENCY-OFF push button has been pressed
while the drive is discharged, the main power supply cannot be connected
to the drive, hence the drive cannot be started up.
The EMERGENCY-OFF push button of the drive is part of the local control
panel (Fig. 8-2) and features a latching switch action.
IMPORTANT! Pressing the EMERGENCY-OFF push button does not
disconnect the auxiliary power supply from the drive.
Note: For more information, see "Emergency off/stop modes and
prevention of operation & safe torque off" (3BHS196243).
8.10.3 Initiating an emergency-off
When an emergency-off is initiated during operation, the following
sequence of events occurs:
1) MCB opens
2) Drive system coasts down
3) DC-link of the drive discharges
4) Status line indication of the CDP control panel alternates between
EmergencyOff and NotReadyOn.
5) EMERGENCY-OFF RESET button flashes
6) SUPPLY OFF push button flashes
An emergency-off is initiated by pressing the EMERGENCY-OFF push
button on the door of the drive control unit or an external EMERGENCY-
OFF push button (if present) linked to the emergency-off circuit.
1 L -> 600.0 rpm
StateINU EmergencyOff
MOTOR SP 0.00 rpm
POWER 0.0 kW
Alternating display message:
EmergencyOff
NotReadyOn

Table of Contents